The product is qualified afterinspection and meets the standardGB/T 14048.11, and it is allowedto leave the factory.

Model and meaning

Scope of application

Dual Power Automatic Transfer Switching Equipment(hereinafterreferred to as switch)in applicable to AC 50Hz or 60Hz,rated operatingvoltage 400V,rated operating current 63A or belowdouble-looppowersupplysystem,the conversion to the selectivitybetween the two-waypower supply according to the requirements,theproduct with shorteircuit,overload,under voltage,voltage lossprotection function,alsowith prepared the fire,double points andoutput switching signal functionEspecially suitable for the need tohave fire protection requirements ofoffice buildings,shopping malls,Banks,railway stations,hospitals andhigh-rise building to install firelighting circuit.

Scope of application

◎ Ambient air temperature upper limit value is not more than+40℃,the lower limit value is not less than-5℃,the average value of 24his no morehan+35℃。

◎ The altitude of the installation site is not more than 2000m.

◎ Atmospheric relative humidity in the ambient air temperature of+40℃not more than 50%,at a lower temperature can have higherhumidity;themonthly average minimum temperature of the wettestmonth is+25℃,Theaverage value of maximum relative humidityis 90%,and taking into accountdue to humidity changes occurredin the frost on the surface of the product,special measures shouldbe taken.

◎ Pollution level II.

◎ Operation place without strong vibration and impact,nocorrosion anddamage to the insulation of harmful gases,noserious dust,no conductiveparticles and explosive dangeroussubstances,no strong electromagneticinterference.

Main technology parameters

Specified heating current lth125A250A630A800A
Rated insulation voltage (Ui)800V
Rated concussion.Withstand voltage(Uimp)8KV
Rated working voltage(Ue)AC400V
Rated current In(A)10A、16A、20A、25A、32A、40A、50A、63A、80A、100A、125A140A、160A、180A、200A、225A、250A315A、350A、400A、500A、630A630A、700A、800A
Using categoryAC33iB
Rated short-circuit connection capacity8kA17kA26kA26kA
Rated short-time withstand current(lcw)5kA10kA12.5kA12.5kA
Transfer time≥55
Control voltageAC220V
Wight2.25.68.58.5

Outline and installation dimensions

SpecificationABCDEHØ
125249111983014836
25030015312836231228
630 800432257218584419512

Terminal connection diagram